ASHRAE 241 - office with clean air

ASHRAE Announces Groundbreaking Standard to Improve Indoor Air Quality

The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) recently approved groundbreaking new guidelines, ASHRAE Standard 241, to reduce the risk of disease transmission in indoor spaces. This standard is a breakthrough in public health and has the potential to drastically reduce the spread of contagious illnesses in places like schools, office buildings, and healthcare facilities.

What Does ASHRAE Standard 241 Mean?

ASHRAE Standard 241, Control of Infectious Aerosols, establishes minimum requirements to reduce the risk of disease transmission by exposure to infectious aerosols in new buildings, existing buildings, and major renovations. Standard 241 provides requirements for air system design, installation, operation, and maintenance.

Standard 241 sets requirements for equivalent clean airflow, the rate of pathogen-free airflow into occupied areas of a building that would have the same effect as the total of outdoor air, filtration of indoor air, and air disinfection by technologies such as germicidal ultraviolet light (GUV). 

This approach allows flexibility to select combinations of technologies to follow the standard that best satisfies economic constraints, practical limitations, and sustainability goals. The standard requires all areas where people gather to have air cleaning systems specifically designed to reduce airborne contaminants, such as bacteria and viruses.

Equivalent Clean Airflow with ASHRAE Standard 241

(numbers are CFM/occupant)
Vertical Old Standards
62.1/170
New Standards
241
% Increase or Multiple
Education 2.8-3.5 8.3 2.4-3.0x
Healthcare Exam Room – 6
Patient Room – 4
Waiting Room – 12
Exam Room – 8
Patient Room – 24
Waiting Room – 40
Exam Room – 33%
Patient Room – 6x
Waiting Room – 3.3x
Office 0.5 1.3 2.6x
Other Public Assembly – 5.4
Religious – 4.4
Public Assembly – 20
Religious – 24
Public Assembly – 3.7x
Religious – 5.5x

How Can Upper-Room GUV Help Meet ASHRAE Standard 241?

It’s important to note that the new ASHRAE Standard 241 presents a new formula for calculating equivalent Outdoor Air, which represents a change in both the target CFM per occupant and the math to achieve that target. In the old 62.1 standard, only true outdoor air brought in by the HVAC system could achieve the target. In the new 241 standard, equivalent clean airflow accounts for true outdoor air plus clean air delivery from filtration both induct and in-room, UV-C, and other mitigations. While there are numerous approaches to meet the new ASHRAE standard, in-room UV-C is the most practical and effective.

Typical HVAC systems achieve 2-3 ACH, operating at 70-80% ‌capacity. Forcing them to run at 100% only achieves 3-4 ACH, well below the new Standard for most space types. Most portable air filters found in HVAC systems are inadequately sized for the volume of air they clean.

Typical filters add 1-3 ACH, meaning you would need to deploy multiple noisy and obstructive devices to clean the air adequately.

Rather than moving, filtering, and otherwise treating air, upper-room GUV disinfects large volumes of air at once using light. In this way, it can efficiently add more than ten eACH to a space, which is the equivalent of changing the air in a room every six minutes with a single device.

Additionally, upper-room systems can be easily added to the plans for a new building or retrofitted into an existing building, unlike HVAC upgrades which take months, if not years, to complete across a large building or campus.

R-Zero’s Beam provides the clean air required by ASHRAE’s new standard while consuming 95% less energy than HVAC solutions and being more cost-efficient than HEPA solutions. This makes upper-room GUV a more sustainable and cost-effective option for providing clean air.

The Importance of Clean Air

This new standard is a reminder of the importance of investing in clean air for employees and patrons of businesses, healthcare facilities, schools, and other organizations. By investing in indoor air quality, organizations can demonstrate their commitment the people that occupy their spaces.

ASHRAE Standard 241 is the first step to improving indoor air quality. ASHRAE’s official recognition that clean air practices to date are not acceptable begins the journey. The tide is changing. You’ll hear more about this in the coming years and decades. Enhanced air cleaning, like UV-C, will be the norm.

More posts you might like

  • Trends Driving Corporate Climate Strategies in 2024

    Research firm Verdantix recently published a study surveying 353 global decision-makers, across 38 countries, on the key trends shaping their corporate climate change strategies in 2024. Currently, net zero targets cover a majority (92%) of global GDP. According to the study, prioritizing compliance, seeking competitive advantage, and aligning with stakeholder requirements are the top three […]

  • Celebrating Earth Day, Today and Everyday

    We are proud to celebrate Earth Day, today and everyday, in our mission of preparing today’s buildings to meet tomorrow’s challenges.  Historically, achieving a balance between building user comfort and experience resulted in increased energy consumption and cost, presenting a significant trade-off for building owners and operators aiming for efficiency and sustainability. R-Zero solutions remove […]

  • Creating Energy-Efficient Outcomes for Your Buildings

    Q&A with R-Zero’s Matt Arneson In honor of Earth Month, we sat down with our in-house expert in energy efficiency, Matt Arneson, to learn more about how customers can drive sustainable outcomes across their buildings. Climate disclosure regulations, both domestic and international, seem to be in the news every week. Are building developers, owners, and […]